Current location - Plastic Surgery and Aesthetics Network - Plastic surgery and beauty - S7200-226 is equipped with universal analog input module 23 1, and PT 100 thermal resistance sensor is equipped with temperature transmitter (measuring range is -50- 100, output is 4-20mA).
S7200-226 is equipped with universal analog input module 23 1, and PT 100 thermal resistance sensor is equipped with temperature transmitter (measuring range is -50- 100, output is 4-20mA).
4mA corresponds to minus 50 degrees, and 20mA corresponds to 100 degrees;

4-20mA corresponds to 6400-32000;

It is best to convert the value of AIW into the actual temperature value in PLC program.

This looks more convenient.