(1) When measuring the grounding resistance with the common voltage-current ratio meter grounding resistance meter (commonly known as "grounding shaking table"), the grounding down lead shall be measured separately from the tower through the grounding device of the tower; Through the grounding device of non-prestressed reinforced concrete pole, the grounding down lead is measured separately from the lightning rod from the top of the pole.
(2) When measuring grounding resistance with clamp-on grounding resistance measuring instrument (commonly known as "hook meter"), it is not allowed to measure the grounding down conductor separately from the tower, and the possible errors should be eliminated by exploring and using the experience of this type of grounding resistance measuring instrument. For lines with insulated grounding wires, the clamp grounding resistance measuring instrument shall not be used to measure the grounding resistance of towers.
(3) Seasonal conversion coefficient of grounding resistance. In the absence of empirical data, please refer to table 1: seasonal conversion coefficient table of grounding resistance. Seasonal conversion coefficient table of grounding resistance
Test month 2, March 4th, September 5th, June 7th, August 10, 165438+ 10 1 65438+February.
Coefficient1.01.61.95 2.41.551.2.